$ EZ-EDS 3.3版本生成的电子数据表[File] DescText = "CJ2M-EIP21 EDS File";$文件说明文本CreateDate = 08-28-2009;$文件创建数据CreateTime = 10:59:49;$文件创建时间ModDate = 08-28-2009;$最后修改数据ModTime = 10:59:49;$最后修改时间修订= 1.0;$ EDS Revision [Device] VendCode = 47;$ Vendor ID VendName = "OMRON Corporation";$ Vendor name ProdType = 12;$设备类型ProdTypeStr = "通信适配器"; $ Device type string ProdCode = 23; $ Product code MajRev = 2; $ Major revision MinRev = 1; $ Minor revision ProdName = "CJ2M-EIP21"; $ Product name [Device Classification] Class1 = EtherNetIP; [Params] Param1 = 0, $ first field shall equal 0 ,"", $ path size, path 0x000C, $ descriptor 0xC7, $ data type : UINT 2, $ data size in bytes "Produced Assembly ID", $ name "", $ units "", $ help string 100,199,100, $ min, max, default data values 1,1,1,0, $ mult, dev, base, offset scaling not used 0,0,0,0, $ mult, dev, base, offset link not used 0; $ decimal places not used Param2 = 0, $ first field shall equal 0 ,"", $ path size, path 0x000C, $ descriptor 0xC7, $ data type : UINT 2, $ data size in bytes "Size", $ name "WORD", $ units "", $ help string 2,40,2, $ min, max, default data values 1,2,1,0, $ mult, dev, base, offset scaling not used 0,0,0,0, $ mult, dev, base, offset link not used 0; $ decimal places not used [Connection Manager] Connection2 = 0x02010002, $ trigger & transport mask $ class 1, cyclic, input-only 0x44640305, $ connection parameters $ fixed size, O=>T heartbeat, T=>O pure data/modeless $ O=>T point to point, scheduled, T=>O multicast/point to point, scheduled, ,0,, $ O=>T RPI, size, format ,Param2,, $ T=>O RPI, size, format ,, $ config part 1 (not used) ,, $ config part 2 (not used) "Input Only (Tag type)",$ connection name "", $ Help string "SYMBOL_ANSI"; $ path Connection1 = 0x02010002, $ trigger & transport mask $ class 1, cyclic, input-only 0x44640305, $ connection parameters $ fixed size, O=>T heartbeat, T=>O pure data/modeless $ O=>T point to point, scheduled, T=>O multicast/point to point, scheduled, ,0,, $ O=>T RPI, size, format ,Param2,, $ T=>O RPI, size, format ,, $ config part 1 (not used) ,, $ config part 2 (not used) "Input Only (ID type)", $ connection name "", $ Help string "20 04 24 01 2C 00 2D 00 [Param1]"; $ path [Port] Port1 = 47_NETC_Chassis, "Backplane", "20 66 24 01", 1; Port2 = TCP, "A", "20 F5 24 01", 2; [Capacity] MaxIOConnections = 32; MaxMsgConnections = 64; MaxConsumersPerMcast = 32; TSpec1 = TxRx, 2, 3000; TSpec2 = TxRx, 42, 3000; [47_UpwardDevice] UpwardDevice = 5, 47, 12, 11, 2, "CJ1W-EIP21 Rev2", 47, 12, 12, 2, "CS1W-EIP21 Rev2", 47, 12, 40, 2, "CS1W-EIP21(NE) Rev2", 47, 12, 14, 2, "CJ1W-EIP21(CJ2)", 47, 12, 13, 2, "CJ2B-EIP21";